Preface
Introduction
Definition
Principle of operation
Terminology
Better Air Flow
Pumping Head
Life Factor
Smaller Fan Motors
Casing
Classification
Thermal Design
Sump
Suction tank/auxiliary tank
Tower Structures
Fills
Sprinkler
Fan/ Fan Blades
Fan Drive Motor
Grills
Drift Eliminators
Installation
Towers
Sprinkler Assembly
Normal Conditions
Water quality Control
Post Erection Checks
Pre-commissioning checks
Maintenance Schedule
 




   
Go To Home Home Search Sitemap
   
   
Check after commissioning
 
• Check motor speed to be as specified in technical data for particular model.
• Check air flow rate as per specification.
• Check water flow rate as per specification.
• Check Power current drawn by fan motor is within limits and as specified.
• Check for abnormal noise or vibration during operation.
• Check sprinkler rotates freely at 5 to 8 rpm or adjust holes to angle so as to achieve correct rpm.
• Sprinkler Revolution Table (assumed at full flow).

•
Model DMB 2117 - DMB 4116
RPM 7 - 12
Model DMA 6616 - DMB 8416
RPM 5 - 8
Model DMA 1260 - DMD 1680
RPM 5 - 7
Model DME 1680 - DMB 1616
RPM 3.5 - 5

•

Ensure water is being distributed evenly over the FRP eliminator plates and there is no carry over from below the eliminator plate water must fall down below evenly, and not pass out.
• Eliminator plate adjustment to be checked to ensure equal distance between fill top and plate bottom.
• Measure Temperature at following locations:
•
i. water inlet.
ii. water outlet / sump.
iii. make up water inlet.
iv. wet bulb / dry bulb temperature of air at inlet to tower at 4 locations equally spaced around tower.
v. wet bulb / dry bulb temperature at outlet of tower above fan.
• Adjust drain valve to give adequate blow down.
• Set float to ensure proper operation and to avoid over flow when plant stops.
   
   
   
   
   


 