Pre-commissioning checks
•
Check level of sump, and fan ensure they are parallel to ground.
•
Check center pipe is vertical and sprinkler arms are all levelled, at right angles to center pipe.
•
Ensure no dirt/other foreign particles are present in sump, suction tank etc. Sweep clean/wash clean.
•
Rotate sprinkler with hand and ensure it is free.
•
Ensure fill top is even.
•
Ensure sprinkler arms are at a contrant level above the fills and that the arms do not rub against/ uneven fills, casing etc.
•
Ensure fan and motor assembly is free.
•
Check all bolts are tight and no loose parts noticed.
•
Fill water in sump and check and eliminate water leaks , if any.
•
Connect correct power (i.e 415V, 50Hz 3PH. AC ) supply to fan and check.
•
Direction of rotation of fan is correct and air is being sucked through screen above sump and discharged vertically upwards.
•
Vibrations are negligible.
•
Fan cable connection are made with lugs, and terminal cover gasket, is tight.
•
Establish water flow and check sprinkler rotates and check any unregulated by pass from sprinkler pipes.